Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Rated voltage
220 - 690V
Rated permanent current Iu
1250A
Overload release current setting
500.0 - 1250A
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
Yes
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
With switched-off indicator
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Degree of protection (IP)
IP20
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
No
With integrated under voltage release
No
Complete device with protection unit
Yes
Type of electrical connection of main circuit
Bolt connection
Motor drive optional
Yes
From same serie
1SDA101272R1 | XT7L 1250 Ekip G Hi-TouchLSIG 1250 4p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Rated voltage
220 .. 690V
Rated permanent current Iu
1250A
Overload release current setting
500.0 .. 1250A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
0
Number of poles
4
Degree of protection (IP)
IP20
Type of control element
Toggle
Position of connection for main current circuit
Front side
Motor drive integrated
With integrated under voltage release
Complete device with protection unit
Type of electrical connection of main circuit
Bolt connection
Motor drive optional
From same serie