Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Rated permanent current Iu1250A
Overload release current setting500.0 - 1250A
Rated voltage220 - 690V
Adjustment range undelayed short-circuit release1875.0 - 18750A
Number of poles3
Degree of protection (IP)IP20
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Position of connection for main current circuitFront side
Suitable for DIN rail (top hat rail) mountingNo
Motor drive optionalYes
Number of auxiliary contacts as change-over contact0
With switched-off indicatorNo
Type of control elementToggle
Integrated earth fault protectionNo
With integrated under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalYes
Number of auxiliary contacts as normally closed contact0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101380R1 | XT7S M 1250 Ekip Touch LSI In1250A 3p FF

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

Rated permanent current Iu

1250A

Overload release current setting

500.0 .. 1250A

Rated voltage

220 .. 690V

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Number of poles

3

Degree of protection (IP)

IP20

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Position of connection for main current circuit

Front side

Suitable for DIN rail (top hat rail) mounting

Motor drive optional

Number of auxiliary contacts as change-over contact

0

With switched-off indicator

Type of control element

Toggle

Integrated earth fault protection

With integrated under voltage release

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as normally closed contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.