Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 - 690V
Adjustment range undelayed short-circuit release
1600 - 16000A
Adjustment range short-term delayed short-circuit release
1600 - 16000A
Overload release current setting
640.0 - 1600A
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
With integrated under voltage release
No
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Yes
Position of connection for main current circuit
Front side
With switched-off indicator
No
Type of control element
Toggle
Integrated earth fault protection
No
Rated permanent current Iu
1600A
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Motor drive integrated
No
Degree of protection (IP)
IP20
Motor drive optional
Yes
From same serie
1SDA101413R1 | XT7S M 1600 Ekip G Dip LS/I In1600 3p FF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 .. 690V
Adjustment range undelayed short-circuit release
1600 .. 16000A
Adjustment range short-term delayed short-circuit release
1600 .. 16000A
Overload release current setting
640.0 .. 1600A
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device fixed built-in technique
With integrated under voltage release
Type of electrical connection of main circuit
Bolt connection
Complete device with protection unit
Position of connection for main current circuit
Front side
With switched-off indicator
Type of control element
Toggle
Integrated earth fault protection
Rated permanent current Iu
1600A
Number of auxiliary contacts as normally closed contact
0
Number of poles
3
Motor drive integrated
Degree of protection (IP)
IP20
Motor drive optional