Overload release current setting400.0 - 1000A
Rated permanent current Iu1000A
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Number of poles3
Type of control elementToggle
Position of connection for main current circuitFront side
Rated voltage220 - 690V
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Degree of protection (IP)IP20
With switched-off indicatorNo
Number of auxiliary contacts as change-over contact0
Adjustment range short-term delayed short-circuit release600.0 - 10000A
DIN rail (top hat rail) mounting optionalYes
Integrated earth fault protectionYes
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1500.0 - 15000A
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101447R1 | XT7H M 1000 Ekip Touch LSIG In1000 3p FF

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

400.0 .. 1000A

Rated permanent current Iu

1000A

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Number of poles

3

Type of control element

Toggle

Position of connection for main current circuit

Front side

Rated voltage

220 .. 690V

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Degree of protection (IP)

IP20

With switched-off indicator

Number of auxiliary contacts as change-over contact

0

Adjustment range short-term delayed short-circuit release

600.0 .. 10000A

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1500.0 .. 15000A

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA