Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA101509R1 | XT7L M 1600 Ekip Touch LSI In1600A 3p FF

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated voltage
220 .. 690V
Rated permanent current Iu
1600A
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Overload release current setting
640.0 .. 1600A
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Number of poles
3
Position of connection for main current circuit
Front side
Motor drive integrated
Type of control element
Toggle
Degree of protection (IP)
IP20
With integrated under voltage release
Motor drive optional
Complete device with protection unit