Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated voltage
220 - 690V
With integrated under voltage release
No
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
1200.0 - 12000A
With switched-off indicator
No
Motor drive optional
Yes
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Motor drive integrated
No
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Yes
Position of connection for main current circuit
Front side
Overload release current setting
320.0 - 800A
Degree of protection (IP)
IP20
Complete device with protection unit
Yes
From same serie
1SDA101518R1 | XT7L M 800 Ekip Touch Meas.LSIG 800 3pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
800A
Rated voltage
220 .. 690V
With integrated under voltage release
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
With switched-off indicator
Motor drive optional
Number of auxiliary contacts as normally closed contact
0
Type of control element
Toggle
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as change-over contact
0
Number of poles
3
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Motor drive integrated
Type of electrical connection of main circuit
Bolt connection
Integrated earth fault protection
Position of connection for main current circuit
Front side
Overload release current setting
320.0 .. 800A
Degree of protection (IP)
IP20
Complete device with protection unit
From same serie