Rated voltage220 - 690V
Adjustment range undelayed short-circuit release2400.0 - 24000A
Device constructionBuilt-in device fixed built-in technique
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Suitable for DIN rail (top hat rail) mountingNo
Overload release current setting640.0 - 1600A
Integrated earth fault protectionYes
Rated permanent current Iu1600A
Number of auxiliary contacts as normally closed contact0
Adjustment range short-term delayed short-circuit release960.0 - 16000A
With integrated under voltage releaseNo
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitFront side
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalYes
Complete device with protection unitYes
Type of control elementToggle
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
Motor drive optionalYes
Degree of protection (IP)IP20
Number of poles3
With switched-off indicatorNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101521R1 | XT7L M 1600 EkipTouchMeas.LSIG 1600 3pFF

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

220 .. 690V

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

Device construction

Built-in device fixed built-in technique

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Suitable for DIN rail (top hat rail) mounting

Overload release current setting

640.0 .. 1600A

Integrated earth fault protection

Rated permanent current Iu

1600A

Number of auxiliary contacts as normally closed contact

0

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

With integrated under voltage release

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Front side

Motor drive integrated

DIN rail (top hat rail) mounting optional

Complete device with protection unit

Type of control element

Toggle

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Motor drive optional

Degree of protection (IP)

IP20

Number of poles

3

With switched-off indicator