Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Rated voltage
220 - 690V
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
No
Number of poles
3
Overload release current setting
400.0 - 1000A
With switched-off indicator
No
Type of control element
Toggle
Position of connection for main current circuit
Front side
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Motor drive optional
Yes
Motor drive integrated
No
Integrated earth fault protection
Yes
Degree of protection (IP)
IP20
1SDA101527R1 | XT7L M 1000 Ekip Hi-Touch LSIG 1000 3pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Rated voltage
220 .. 690V
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
0
With integrated under voltage release
Number of poles
3
Overload release current setting
400.0 .. 1000A
With switched-off indicator
Type of control element
Toggle
Position of connection for main current circuit
Front side
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
Motor drive integrated
Integrated earth fault protection
Degree of protection (IP)
IP20