Technical specifications
Overload release current setting
640.0 - 1600A
Rated permanent current Iu
1600A
Rated voltage
220 - 690V
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
No
DIN rail (top hat rail) mounting optional
Yes
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of poles
3
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Motor drive integrated
No
Type of control element
Toggle
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Motor drive optional
Yes
From same serie
1SDA101549R1 | XT7L M 1600 EkipG Hi-TouchLSIG 1600 3pFF

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
640.0 .. 1600A
Rated permanent current Iu
1600A
Rated voltage
220 .. 690V
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
DIN rail (top hat rail) mounting optional
Device construction
Built-in device fixed built-in technique
Position of connection for main current circuit
Front side
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of poles
3
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Motor drive integrated
Type of control element
Toggle
Complete device with protection unit
Degree of protection (IP)
IP20
Motor drive optional
From same serie