Technical specifications

Adjustment range short-term delayed short-circuit release

480.0 - 8000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Rated permanent current Iu

800A

Suitable for DIN rail (top hat rail) mounting

No

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

0

With integrated under voltage release

No

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Yes

Integrated earth fault protection

Yes

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

No

With switched-off indicator

No

Number of poles

4

Position of connection for main current circuit

Front side

Motor drive optional

Yes

Overload release current setting

320.0 - 800A

Type of control element

Toggle

Rated voltage

220 - 690V

Complete device with protection unit

Yes

Adjustment range undelayed short-circuit release

1200.0 - 12000A

Degree of protection (IP)

IP20


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA101698R1 | XT7S M 800 Ekip G Hi-Touch LSIG 800 4pFF

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Rated permanent current Iu

800A

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

0

With integrated under voltage release

Type of electrical connection of main circuit

Bolt connection

DIN rail (top hat rail) mounting optional

Integrated earth fault protection

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

With switched-off indicator

Number of poles

4

Position of connection for main current circuit

Front side

Motor drive optional

Overload release current setting

320.0 .. 800A

Type of control element

Toggle

Rated voltage

220 .. 690V

Complete device with protection unit

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Degree of protection (IP)

IP20