Technical specifications

Number of poles4
Overload release current setting320.0 - 800A
Rated permanent current Iu800A
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitFront side
Type of electrical connection of main circuitBolt connection
Degree of protection (IP)IP20
Number of auxiliary contacts as change-over contact0
Rated voltage220 - 690V
Motor drive integratedNo
Type of control elementToggle
Adjustment range undelayed short-circuit release1200.0 - 12000A
Motor drive optionalYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
With switched-off indicatorNo
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalYes
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101722R1 | XT7H M 800 Ekip Touch LSI In=800A 4p F F

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Overload release current setting

320.0 .. 800A

Rated permanent current Iu

800A

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Number of auxiliary contacts as normally open contact

0

Position of connection for main current circuit

Front side

Type of electrical connection of main circuit

Bolt connection

Degree of protection (IP)

IP20

Number of auxiliary contacts as change-over contact

0

Rated voltage

220 .. 690V

Motor drive integrated

Type of control element

Toggle

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Motor drive optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

With switched-off indicator

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Complete device with protection unit