Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Overload release current setting400 - 1000A
Degree of protection (IP)IP20
Adjustment range short-term delayed short-circuit release600 - 10000A
Number of auxiliary contacts as change-over contact0
With integrated under voltage releaseNo
Device constructionBuilt-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalYes
Number of auxiliary contacts as normally closed contact0
Integrated earth fault protectionYes
Type of electrical connection of main circuitBolt connection
With switched-off indicatorNo
Motor drive integratedNo
Type of control elementToggle
Adjustment range undelayed short-circuit release1500 - 15000A
Position of connection for main current circuitFront side
Complete device with protection unitYes
Motor drive optionalYes
Rated permanent current Iu1000A
Number of poles4
Rated voltage220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user