Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Overload release current setting320 - 800A
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Degree of protection (IP)IP20
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitBolt connection
With switched-off indicatorNo
Adjustment range undelayed short-circuit release1200 - 12000A
Complete device with protection unitYes
Type of control elementToggle
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release480 - 8000A
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalYes
Motor drive integratedNo
Rated permanent current Iu800A
Number of poles4
Rated voltage220 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA