Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Position of connection for main current circuitFront side
Rated voltage220 - 690V
Rated permanent current Iu800A
Number of poles4
Integrated earth fault protectionYes
Degree of protection (IP)IP20
Adjustment range short-term delayed short-circuit release480.0 - 8000A
With integrated under voltage releaseNo
Type of electrical connection of main circuitBolt connection
Overload release current setting320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz120kA
Number of auxiliary contacts as change-over contact0
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release1200.0 - 12000A
Motor drive integratedNo
Type of control elementToggle
With switched-off indicatorNo
DIN rail (top hat rail) mounting optionalYes
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA101790R1 | XT7L M 800 Ekip Touch Meas.LSIG 800 4pFF

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Position of connection for main current circuit

Front side

Rated voltage

220 .. 690V

Rated permanent current Iu

800A

Number of poles

4

Integrated earth fault protection

Degree of protection (IP)

IP20

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

With integrated under voltage release

Type of electrical connection of main circuit

Bolt connection

Overload release current setting

320.0 .. 800A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

120kA

Number of auxiliary contacts as change-over contact

0

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Motor drive integrated

Type of control element

Toggle

With switched-off indicator

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

Complete device with protection unit