Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Rated permanent current Iu
1250A
Rated voltage
220 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
1250 - 12500A
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Yes
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
500.0 - 1250A
Integrated earth fault protection
No
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Type of control element
Toggle
Position of connection for main current circuit
Front side
With integrated under voltage release
No
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP20
1SDA101820R1 | XT7L M 1250 Ekip Dip LIG In=1250A 4p F F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Rated permanent current Iu
1250A
Rated voltage
220 .. 690V
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
1250 .. 12500A
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Overload release current setting
500.0 .. 1250A
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
120kA
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Type of control element
Toggle
Position of connection for main current circuit
Front side
With integrated under voltage release
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP20