Number of auxiliary contacts as normally open contact0
Rated permanent current Iu800A
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Overload release current setting441.0 - 630A
Number of poles4
Rated voltage220 - 690V
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Degree of protection (IP)IP20
Motor drive integratedNo
Adjustment range undelayed short-circuit release3150 - 6300A
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalYes
Device constructionBuilt-in device fixed built-in technique
Type of electrical connection of main circuitBolt connection
Integrated earth fault protectionNo
Adjustment range short-term delayed short-circuit release- - -A
With switched-off indicatorNo
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz36kA
Complete device with protection unitYes
Type of control elementToggle
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA107569R1 | XT6N 800 TMA 630-6300 4p F F InN=100%In

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

800A

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Overload release current setting

441.0 .. 630A

Number of poles

4

Rated voltage

220 .. 690V

Number of auxiliary contacts as change-over contact

0

Position of connection for main current circuit

Front side

Degree of protection (IP)

IP20

Motor drive integrated

Adjustment range undelayed short-circuit release

3150 .. 6300A

Motor drive optional

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

- .. -A

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

36kA

Complete device with protection unit

Type of control element

Toggle