Rated voltage230V
Built-in depth68.9mm
Voltage typeAC
Rated current32A
Rated insulation voltage Ui500V
Current limiting class3
Release characteristicB
Surge current capacity0.25kA
Leakage current typeAC
Over voltage category3
Power loss5.2W
Rated fault current0.03A
Width in number of modular spacings1
Degree of protection (IP)IP2X
Number of protected poles1
Frequency50/60 Hz
Suitable for flush-mounted installationNo
Rated short-circuit breaking capacity according to EN 608986kA
Flush-mounted installationNo
With interlocking deviceYes
Concurrently switching neutral conductorNo
Rated impulse withstand voltage Uimp4kV
Ambient temperature during operating-25 - 55°C
Anti-nuisance tripping versionNo
Pollution degree2
Rated short-circuit breaking capacity according to IEC 60947-26kA
Number of poles (total)2
Connectable conductor cross section solid-core1 - 25mm²
Connectable conductor cross section multi-wired1 - 16mm²
Disconnection characteristicUndelayed
Rated short-circuit breaking capacity Icn according to EN 61009-16kA
Rated short-circuit breaking capacity according to EN 610096kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

2CSR255051R1325 | DSE201 B32 AC30

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • ABB

Technical specifications

Rated voltage

230V

Built-in depth

68.9mm

Voltage type

AC

Rated current

32A

Rated insulation voltage Ui

500V

Current limiting class

3

Release characteristic

B

Surge current capacity

0.25kA

Leakage current type

AC

Over voltage category

3

Power loss

5.2W

Rated fault current

0.03A

Width in number of modular spacings

1

Degree of protection (IP)

IP2X

Number of protected poles

1

Frequency

50/60 Hz

Suitable for flush-mounted installation

Rated short-circuit breaking capacity according to EN 60898

6kA

Flush-mounted installation

With interlocking device

Concurrently switching neutral conductor

Rated impulse withstand voltage Uimp

4kV

Ambient temperature during operating

-25 .. 55°C

Anti-nuisance tripping version

Pollution degree

2

Rated short-circuit breaking capacity according to IEC 60947-2

6kA

Number of poles (total)

2

Connectable conductor cross section solid-core

1 .. 25mm²

Connectable conductor cross section multi-wired

1 .. 16mm²

Disconnection characteristic

Undelayed

Rated short-circuit breaking capacity Icn according to EN 61009-1

6kA

Rated short-circuit breaking capacity according to EN 61009

6kA