Technical specifications

Width81mm
Number of poles3
Rated permanent current Iu115A
Height155mm
Rated operating voltage690 - 690V
With integrated under voltage releaseNo
With integrated auxiliary switchNo
Thermal protectionNo
Rated operation power at AC-3, 400 V55kW
Depth165mm
Overload release current setting- - -A
Adjustment range undelayed short-circuit release690 - 1610A
Type of control elementTurn button
Type of electrical connection of main circuitScrew connection
Rated short-circuit breaking capacity lcu at 400 V, AC100kA
Switch off techniqueMagnetic
With thermal protectionNo
Degree of protection (IP)IP40
Rated operation power at AC-3, 230 V30kW
Phase failure sensitiveNo
Device constructionComplete device in housing
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GV4L115S | Prekidac Motorski GV4L 115A 100KA Elink

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Motor protection circuit-breaker
  • 1 KOM
  • SCHNEIDER

Technical specifications

Width

81mm

Number of poles

3

Rated permanent current Iu

115A

Height

155mm

Rated operating voltage

690 .. 690V

With integrated under voltage release

With integrated auxiliary switch

Thermal protection

Rated operation power at AC-3, 400 V

55kW

Depth

165mm

Overload release current setting

- .. -A

Adjustment range undelayed short-circuit release

690 .. 1610A

Type of control element

Turn button

Type of electrical connection of main circuit

Screw connection

Rated short-circuit breaking capacity lcu at 400 V, AC

100kA

Switch off technique

Magnetic

With thermal protection

Degree of protection (IP)

IP40

Rated operation power at AC-3, 230 V

30kW

Phase failure sensitive

Device construction

Complete device in housing

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.