Technical specifications

With transformerNo
Number of command positions0
Power consumption2.6W
Width45mm
Depth76mm
Height170mm
Suitable for emergency stopNo
Number of indicator lights0
Supporting protocol for LONNo
Supporting protocol for Data-HighwayNo
Supporting protocol for ModbusNo
Supporting protocol for PROFIBUSNo
Supporting protocol for INTERBUSNo
Supporting protocol for CANNo
Supporting protocol for DeviceNetNo
Supporting protocol for SUCONETNo
Supporting protocol for TCP/IPNo
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact1
External reset possibleNo
Supporting protocol for other bus systemsNo
Supporting protocol for ASINo
Release classCLASS 10 A
Rated control supply voltage Us at AC 60HZ0 - 0V
Rated control supply voltage Us at AC 50HZ0 - 0V
With fuseNo
With short-circuit releaseYes
Supporting protocol for SERCOSNo
Supporting protocol for INTERBUS-SafetyNo
Rail mounting possibleNo
Supporting protocol for AS-Interface Safety at WorkNo
Supporting protocol for PROFIsafeNo
Supporting protocol for Foundation FieldbusNo
Supporting protocol for DeviceNet SafetyNo
Type of electrical connection for auxiliary- and control current circuitScrew connection
Supporting protocol for EtherNet/IPNo
Type of electrical connection of main circuitScrew connection
Supporting protocol for PROFINET CBANo
Rated power, 460 V, 60 Hz, 3-phase0kW
Rated operation power at AC-3, 230 V, 3-phase0.25kW
Voltage type for actuatingDC
Supporting protocol for SafetyBUS pNo
Rated power, 575 V, 60 Hz, 3-phase0kW
Supporting protocol for PROFINET IONo
Rated conditional short-circuit current, type 1, 600 Y/347 V0A
Rated conditional short-circuit current, type 2, 230 V50000A
Ambient temperature, upper operating limit55°C
Rated conditional short-circuit current, type 2, 400 V50000A
Temperature compensated overload protectionYes
Degree of protection (NEMA)Other
Rated conditional short-circuit current, type 1, 480 Y/277 V0A
Coordination class according to IEC 60947-4-3Class 2
Rated operation power at AC-3, 400 V0.55kW
Rated operation current Ie1.5A
Overload release current setting1 - 1.6A
Degree of protection (IP)IP20
Rated control supply voltage Us at DC24 - 24V
Type of motor starterDirect online starter (DOL)
Rated operation current at AC-3, 400 V1.6A