Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
630A
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1.5 - 7A
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1260 - 10080A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
Motor drive integrated
No
Type of control element
Rocker lever
With integrated under voltage release
No
Position of connection for main current circuit
Front side
With switched-off indicator
No
Degree of protection (IP)
IP20
Integrated earth fault protection
Yes
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Overload release current setting
252 - 630A
Motor drive optional
Yes
From same serie
NZMH3-4-VX630-T

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
630A
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1.5 .. 7A
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1260 .. 10080A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Screw connection
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Motor drive integrated
Type of control element
Rocker lever
With integrated under voltage release
Position of connection for main current circuit
Front side
With switched-off indicator
Degree of protection (IP)
IP20
Integrated earth fault protection
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Overload release current setting
252 .. 630A
Motor drive optional