Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu630A
Device constructionBuilt-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release1.5 - 7A
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
Adjustment range undelayed short-circuit release1260 - 10080A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitScrew connection
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally closed contact0
Complete device with protection unitYes
Motor drive integratedNo
Type of control elementRocker lever
With integrated under voltage releaseNo
Position of connection for main current circuitFront side
With switched-off indicatorNo
Degree of protection (IP)IP20
Integrated earth fault protectionYes
Number of poles4
Number of auxiliary contacts as normally open contact0
Overload release current setting252 - 630A
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMH3-4-VX630-T

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

630A

Device construction

Built-in device fixed built-in technique

Adjustment range short-term delayed short-circuit release

1.5 .. 7A

Suitable for DIN rail (top hat rail) mounting

Rated voltage

690 .. 690V

Adjustment range undelayed short-circuit release

1260 .. 10080A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

DIN rail (top hat rail) mounting optional

Type of electrical connection of main circuit

Screw connection

Number of auxiliary contacts as change-over contact

0

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

Motor drive integrated

Type of control element

Rocker lever

With integrated under voltage release

Position of connection for main current circuit

Front side

With switched-off indicator

Degree of protection (IP)

IP20

Integrated earth fault protection

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Overload release current setting

252 .. 630A

Motor drive optional