Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorNo
Adjustment range short-term delayed short-circuit release2 - 10A
Adjustment range undelayed short-circuit release2 - 18A
Degree of protection (IP)IP20
Type of electrical connection of main circuitScrew connection
Overload release current setting40 - 100A
Number of auxiliary contacts as change-over contact0
Type of control elementRocker lever
DIN rail (top hat rail) mounting optionalYes
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionNo
Motor drive optionalYes
Position of connection for main current circuitFront side
Complete device with protection unitYes
With integrated under voltage releaseNo
Rated permanent current Iu100A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA