Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Overload release current setting252 - 630A
With switched-off indicatorNo
Motor drive integratedNo
Type of control elementRocker lever
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Adjustment range short-term delayed short-circuit release1.5 - 7A
Adjustment range undelayed short-circuit release1260 - 10080A
Type of electrical connection of main circuitOther
Degree of protection (IP)IP20
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
Integrated earth fault protectionNo
Rated permanent current Iu630A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA