Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Type of electrical connection of main circuitScrew connection
Device constructionBuilt-in device fixed built-in technique
Adjustment range undelayed short-circuit release2 - 18A
Suitable for DIN rail (top hat rail) mountingNo
Number of poles4
Number of auxiliary contacts as change-over contact0
Rated permanent current Iu250A
With switched-off indicatorNo
Motor drive integratedNo
With integrated under voltage releaseNo
Adjustment range short-term delayed short-circuit release2 - 10A
Type of control elementRocker lever
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
DIN rail (top hat rail) mounting optionalNo
Overload release current setting100 - 250A
Degree of protection (IP)IP20
Position of connection for main current circuitFront side
Integrated earth fault protectionYes
Rated voltage690 - 690V
Number of auxiliary contacts as normally open contact0
Motor drive optionalYes
Number of auxiliary contacts as normally closed contact0
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMS3-4-PX250/VAR-TAZ

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Type of electrical connection of main circuit

Screw connection

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

2 .. 18A

Suitable for DIN rail (top hat rail) mounting

Number of poles

4

Number of auxiliary contacts as change-over contact

0

Rated permanent current Iu

250A

With switched-off indicator

Motor drive integrated

With integrated under voltage release

Adjustment range short-term delayed short-circuit release

2 .. 10A

Type of control element

Rocker lever

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

DIN rail (top hat rail) mounting optional

Overload release current setting

100 .. 250A

Degree of protection (IP)

IP20

Position of connection for main current circuit

Front side

Integrated earth fault protection

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally open contact

0

Motor drive optional

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.