Technical specifications

Type of electrical connection of main circuitScrew connection
Device constructionBuilt-in device fixed built-in technique
Adjustment range undelayed short-circuit release2 - 18A
Suitable for DIN rail (top hat rail) mountingNo
Number of auxiliary contacts as change-over contact0
With switched-off indicatorNo
Motor drive integratedNo
With integrated under voltage releaseNo
Adjustment range short-term delayed short-circuit release2 - 10A
Type of control elementRocker lever
DIN rail (top hat rail) mounting optionalNo
Overload release current setting100 - 250A
Degree of protection (IP)IP20
Position of connection for main current circuitFront side
Integrated earth fault protectionYes
Number of auxiliary contacts as normally open contact0
Motor drive optionalYes
Number of auxiliary contacts as normally closed contact0
Complete device with protection unitYes
Rated permanent current Iu250A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMS3-4-PX250/VAR-TAZ

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Type of electrical connection of main circuit

Screw connection

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

2 .. 18A

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as change-over contact

0

With switched-off indicator

Motor drive integrated

With integrated under voltage release

Adjustment range short-term delayed short-circuit release

2 .. 10A

Type of control element

Rocker lever

DIN rail (top hat rail) mounting optional

Overload release current setting

100 .. 250A

Degree of protection (IP)

IP20

Position of connection for main current circuit

Front side

Integrated earth fault protection

Number of auxiliary contacts as normally open contact

0

Motor drive optional

Number of auxiliary contacts as normally closed contact

0

Complete device with protection unit

Rated permanent current Iu

250A

Number of poles

4

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA