Technical specifications

Rated permanent current Iu630A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz70kA
Overload release current setting252 - 630A
Rated voltage690 - 690V
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitScrew connection
Adjustment range undelayed short-circuit release1260 - 10080A
Adjustment range short-term delayed short-circuit release1.5 - 7A
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally open contact0
DIN rail (top hat rail) mounting optionalNo
Number of poles3
Position of connection for main current circuitFront side
With switched-off indicatorNo
With integrated under voltage releaseNo
Complete device with protection unitYes
Type of control elementRocker lever
Motor drive optionalYes
Degree of protection (IP)IP20
Motor drive integratedNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

NZMS3-VX630

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • EATON

Technical specifications

Rated permanent current Iu

630A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

70kA

Overload release current setting

252 .. 630A

Rated voltage

690 .. 690V

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Screw connection

Adjustment range undelayed short-circuit release

1260 .. 10080A

Adjustment range short-term delayed short-circuit release

1.5 .. 7A

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

0

Number of auxiliary contacts as normally open contact

0

DIN rail (top hat rail) mounting optional

Number of poles

3

Position of connection for main current circuit

Front side

With switched-off indicator

With integrated under voltage release

Complete device with protection unit

Type of control element

Rocker lever

Motor drive optional

Degree of protection (IP)

IP20

Motor drive integrated