Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Built-in depth72mm
Explosion-proofNo
Release characteristicC
Current limiting class3
Pollution degree3
Width in number of modular spacings1
Voltage typeAC
Rated insulation voltage Ui500V
Rated current32A
Power loss6.9W
Degree of protection (IP)IP20
Over voltage category3
Frequency50 - 60Hz
Number of protected poles2
Concurrently switching neutral conductorNo
Ambient temperature during operating-25 - 60°C
Connectable conductor cross section solid-core16 - 16mm²
Connectable conductor cross section multi-wired10 - 10mm²
Rated voltage230V
Rated impulse withstand voltage Uimp4kV
Number of poles (total)2
Flush-mounted installationNo
Additional equipment possibleYes
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V4.5kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V6kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW90050

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Built-in depth

72mm

Explosion-proof

Release characteristic

C

Current limiting class

3

Pollution degree

3

Width in number of modular spacings

1

Voltage type

AC

Rated insulation voltage Ui

500V

Rated current

32A

Power loss

6.9W

Degree of protection (IP)

IP20

Over voltage category

3

Frequency

50 .. 60Hz

Number of protected poles

2

Concurrently switching neutral conductor

Ambient temperature during operating

-25 .. 60°C

Connectable conductor cross section solid-core

16 .. 16mm²

Connectable conductor cross section multi-wired

10 .. 10mm²

Rated voltage

230V

Rated impulse withstand voltage Uimp

4kV

Number of poles (total)

2

Flush-mounted installation

Additional equipment possible

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

4.5kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

6kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.