

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- GEWISS
Technical specifications
Built-in depth
72mm
Release characteristic
C
Number of poles (total)
2
Rated current
2A
Number of protected poles
2
Rated impulse withstand voltage Uimp
4kV
Rated insulation voltage Ui
500V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6kA
Rated voltage
400V
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
6kA
Voltage type
AC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
20kA
Frequency
50 - 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
10kA
Power loss
5.4W
Current limiting class
3
Flush-mounted installation
No
Concurrently switching neutral conductor
No
Over voltage category
3
Pollution degree
3
Additional equipment possible
Yes
Degree of protection (IP)
IP20
Width in number of modular spacings
2
Ambient temperature during operating
-25 - 60°C
Explosion-proof
No
Connectable conductor cross section solid-core
35 - 35mm²
Connectable conductor cross section multi-wired
35 - 35mm²
GW92042

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- GEWISS
Technical specifications
Built-in depth
72mm
Release characteristic
C
Number of poles (total)
2
Rated current
2A
Number of protected poles
2
Rated impulse withstand voltage Uimp
4kV
Rated insulation voltage Ui
500V
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6kA
Rated voltage
400V
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
6kA
Voltage type
AC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
20kA
Frequency
50 .. 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
10kA
Power loss
5.4W
Current limiting class
3
Flush-mounted installation
Concurrently switching neutral conductor
Over voltage category
3
Pollution degree
3
Additional equipment possible
Degree of protection (IP)
IP20
Width in number of modular spacings
2
Ambient temperature during operating
-25 .. 60°C
Explosion-proof
Connectable conductor cross section solid-core
35 .. 35mm²
Connectable conductor cross section multi-wired
35 .. 35mm²
We use cookies to enhance your experience.