Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Power loss7.46W
Frequency50 - 60Hz
Current limiting class3
Width in number of modular spacings2
Pollution degree3
Rated voltage400V
Over voltage category3
Degree of protection (IP)IP20
Number of protected poles2
Voltage typeAC
Concurrently switching neutral conductorNo
Built-in depth72mm
Rated insulation voltage Ui500V
Explosion-proofNo
Rated current40A
Release characteristicC
Connectable conductor cross section solid-core35 - 35mm²
Connectable conductor cross section multi-wired35 - 35mm²
Ambient temperature during operating-25 - 60°C
Flush-mounted installationNo
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V20kA
Additional equipment possibleYes
Number of poles (total)2
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V6kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V6kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW92051

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Power loss

7.46W

Frequency

50 .. 60Hz

Current limiting class

3

Width in number of modular spacings

2

Pollution degree

3

Rated voltage

400V

Over voltage category

3

Degree of protection (IP)

IP20

Number of protected poles

2

Voltage type

AC

Concurrently switching neutral conductor

Built-in depth

72mm

Rated insulation voltage Ui

500V

Explosion-proof

Rated current

40A

Release characteristic

C

Connectable conductor cross section solid-core

35 .. 35mm²

Connectable conductor cross section multi-wired

35 .. 35mm²

Ambient temperature during operating

-25 .. 60°C

Flush-mounted installation

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

20kA

Additional equipment possible

Number of poles (total)

2

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

6kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

6kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.