Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Number of protected poles2
Built-in depth72mm
Rated voltage400V
Power loss4.48W
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
Over voltage category3
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V6kA
Current limiting class3
Voltage typeAC
Rated insulation voltage Ui500V
Concurrently switching neutral conductorNo
Frequency50 - 60Hz
Pollution degree3
Flush-mounted installationNo
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V20kA
Additional equipment possibleYes
Ambient temperature during operating-25 - 60°C
Connectable conductor cross section multi-wired35 - 35mm²
Explosion-proofNo
Connectable conductor cross section solid-core35 - 35mm²
Width in number of modular spacings2
Degree of protection (IP)IP20
Rated current25A
Release characteristicB
Number of poles (total)2
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V6kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW92249 | MCB 2P B25 6KA 2M

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Number of protected poles

2

Built-in depth

72mm

Rated voltage

400V

Power loss

4.48W

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

Over voltage category

3

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

6kA

Current limiting class

3

Voltage type

AC

Rated insulation voltage Ui

500V

Concurrently switching neutral conductor

Frequency

50 .. 60Hz

Pollution degree

3

Flush-mounted installation

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

20kA

Additional equipment possible

Ambient temperature during operating

-25 .. 60°C

Connectable conductor cross section multi-wired

35 .. 35mm²

Explosion-proof

Connectable conductor cross section solid-core

35 .. 35mm²

Width in number of modular spacings

2

Degree of protection (IP)

IP20

Rated current

25A

Release characteristic

B

Number of poles (total)

2

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

6kA