  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Voltage typeAC
Pollution degree3
Rated current50A
Frequency50 - 60Hz
Built-in depth72mm
Over voltage category3
Current limiting class3
Number of protected poles3
Width in number of modular spacings3
Release characteristicB
Rated insulation voltage Ui500V
Concurrently switching neutral conductorNo
Rated voltage400V
Power loss14.34W
Explosion-proofNo
Connectable conductor cross section multi-wired35 - 35mm²
Degree of protection (IP)IP20
Connectable conductor cross section solid-core35 - 35mm²
Ambient temperature during operating-25 - 60°C
Additional equipment possibleYes
Flush-mounted installationNo
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V6kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
Number of poles (total)3
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V6kA
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V20kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW92272

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Voltage type

AC

Pollution degree

3

Rated current

50A

Frequency

50 .. 60Hz

Built-in depth

72mm

Over voltage category

3

Current limiting class

3

Number of protected poles

3

Width in number of modular spacings

3

Release characteristic

B

Rated insulation voltage Ui

500V

Concurrently switching neutral conductor

Rated voltage

400V

Power loss

14.34W

Explosion-proof

Connectable conductor cross section multi-wired

35 .. 35mm²

Degree of protection (IP)

IP20

Connectable conductor cross section solid-core

35 .. 35mm²

Ambient temperature during operating

-25 .. 60°C

Additional equipment possible

Flush-mounted installation

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

6kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

Number of poles (total)

3

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

6kA

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

20kA