Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Explosion-proofNo
Rated voltage400V
Frequency50 - 60Hz
Pollution degree3
Degree of protection (IP)IP20
Over voltage category3
Power loss4.68W
Rated insulation voltage Ui500V
Width in number of modular spacings2
Rated current32A
Current limiting class3
Built-in depth72mm
Voltage typeAC
Release characteristicD
Number of protected poles2
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V6kA
Additional equipment possibleYes
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V10kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V6kA
Number of poles (total)2
Flush-mounted installationNo
Ambient temperature during operating-25 - 60°C
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V20kA
Connectable conductor cross section multi-wired35 - 35mm²
Connectable conductor cross section solid-core35 - 35mm²
Concurrently switching neutral conductorNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW92450

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Explosion-proof

Rated voltage

400V

Frequency

50 .. 60Hz

Pollution degree

3

Degree of protection (IP)

IP20

Over voltage category

3

Power loss

4.68W

Rated insulation voltage Ui

500V

Width in number of modular spacings

2

Rated current

32A

Current limiting class

3

Built-in depth

72mm

Voltage type

AC

Release characteristic

D

Number of protected poles

2

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

6kA

Additional equipment possible

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

10kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

6kA

Number of poles (total)

2

Flush-mounted installation

Ambient temperature during operating

-25 .. 60°C

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

20kA

Connectable conductor cross section multi-wired

35 .. 35mm²

Connectable conductor cross section solid-core

35 .. 35mm²

Concurrently switching neutral conductor