Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Voltage typeAC
Built-in depth72mm
Rated impulse withstand voltage Uimp4kV
Number of poles (total)2
Rated current50A
Ambient temperature during operating-25 - 60°C
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V15kA
Width in number of modular spacings2
Flush-mounted installationNo
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V25kA
Pollution degree2
Concurrently switching neutral conductorNo
Degree of protection (IP)IP20
Connectable conductor cross section solid-core35 - 35mm²
Power loss9.56W
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V25kA
Additional equipment possibleYes
Release characteristicC
Rated insulation voltage Ui500V
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V15kA
Explosion-proofNo
Number of protected poles2
Connectable conductor cross section multi-wired35 - 35mm²
Over voltage category3
Rated voltage400V
Frequency50 - 60Hz
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW92852

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Voltage type

AC

Built-in depth

72mm

Rated impulse withstand voltage Uimp

4kV

Number of poles (total)

2

Rated current

50A

Ambient temperature during operating

-25 .. 60°C

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

15kA

Width in number of modular spacings

2

Flush-mounted installation

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

25kA

Pollution degree

2

Concurrently switching neutral conductor

Degree of protection (IP)

IP20

Connectable conductor cross section solid-core

35 .. 35mm²

Power loss

9.56W

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

25kA

Additional equipment possible

Release characteristic

C

Rated insulation voltage Ui

500V

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

15kA

Explosion-proof

Number of protected poles

2

Connectable conductor cross section multi-wired

35 .. 35mm²

Over voltage category

3

Rated voltage

400V

Frequency

50 .. 60Hz

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.