Details
- •Circuit breakers and fuses
- •Miniature circuit breaker (MCB)
- •1 KOM
- •GEWISS
Technical specifications
GW93338

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- GEWISS
Technical specifications
Concurrently switching neutral conductor
Voltage type
AC
Built-in depth
72mm
Rated current
100A
Number of protected poles
3
Release characteristic
C
Explosion-proof
Rated voltage
400V
Power loss
22.2W
Rated insulation voltage Ui
500V
Width in number of modular spacings
4.5
Frequency
50 .. 60Hz
Connectable conductor cross section solid-core
70 .. 70mm²
Pollution degree
2
Over voltage category
4
Degree of protection (IP)
IP20
Connectable conductor cross section multi-wired
50 .. 50mm²
Ambient temperature during operating
-25 .. 60°C
Additional equipment possible
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
10kA
Rated impulse withstand voltage Uimp
6kV
Flush-mounted installation
Number of poles (total)
3
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
20kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
16kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
10kA