Aleta.hr

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Built-in depth72mm
Release characteristicD
Frequency50 - 60Hz
Number of poles (total)4
Rated current63A
Number of protected poles4
Rated voltage400V
Rated insulation voltage Ui500V
Rated impulse withstand voltage Uimp6kV
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V10kA
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V20kA
Voltage typeAC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V16kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V10kA
Over voltage category4
Power loss22.4W
Pollution degree2
Concurrently switching neutral conductorNo
Flush-mounted installationNo
Additional equipment possibleYes
Degree of protection (IP)IP20
Ambient temperature during operating-25 - 60°C
Explosion-proofNo
Width in number of modular spacings6
Connectable conductor cross section solid-core70 - 70mm²
Connectable conductor cross section multi-wired50 - 50mm²
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW93396 | High Perf. MCB 4P D63 16KA 6M

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Miniature circuit breaker (MCB)
  • 1 KOM
  • GEWISS

Technical specifications

Built-in depth

72mm

Release characteristic

D

Frequency

50 .. 60Hz

Number of poles (total)

4

Rated current

63A

Number of protected poles

4

Rated voltage

400V

Rated insulation voltage Ui

500V

Rated impulse withstand voltage Uimp

6kV

Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V

10kA

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V

20kA

Voltage type

AC

Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V

16kA

Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V

10kA

Over voltage category

4

Power loss

22.4W

Pollution degree

2

Concurrently switching neutral conductor

Flush-mounted installation

Additional equipment possible

Degree of protection (IP)

IP20

Ambient temperature during operating

-25 .. 60°C

Explosion-proof

Width in number of modular spacings

6

Connectable conductor cross section solid-core

70 .. 70mm²

Connectable conductor cross section multi-wired

50 .. 50mm²

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.