Aleta.hr

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • GEWISS

Technical specifications

Number of protected poles1
Rated voltage230V
Rated insulation voltage Ui500V
Power loss20W
Rated short-circuit breaking capacity according to EN 610096kA
Current limiting class3
Rated impulse withstand voltage Uimp4kV
Rated short-circuit breaking capacity according to IEC 60947-210kA
Disconnection characteristicUndelayed
Rated short-circuit breaking capacity Icn according to EN 61009-16kA
Surge current capacity0.25kA
Built-in depth72mm
Concurrently switching neutral conductorYes
Anti-nuisance tripping versionNo
With interlocking deviceNo
Voltage typeAC
Pollution degree2
Over voltage category3
Release characteristicC
Flush-mounted installationNo
Frequency50/60 Hz
Ambient temperature during operating-25 - 40°C
Width in number of modular spacings2
Degree of protection (IP)IP20
Connectable conductor cross section solid-core35 - 35mm²
Connectable conductor cross section multi-wired35 - 35mm²
Rated current20A
Rated fault current0.3A
Leakage current typeA
Number of poles (total)2
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW94318 | Compact RCBO 1P+N C20 6KA A/0.3 2M

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Circuit breakers and fuses
  • Earth leakage circuit breaker
  • 1 KOM
  • GEWISS

Technical specifications

Number of protected poles

1

Rated voltage

230V

Rated insulation voltage Ui

500V

Power loss

20W

Rated short-circuit breaking capacity according to EN 61009

6kA

Current limiting class

3

Rated impulse withstand voltage Uimp

4kV

Rated short-circuit breaking capacity according to IEC 60947-2

10kA

Disconnection characteristic

Undelayed

Rated short-circuit breaking capacity Icn according to EN 61009-1

6kA

Surge current capacity

0.25kA

Built-in depth

72mm

Concurrently switching neutral conductor

Anti-nuisance tripping version

With interlocking device

Voltage type

AC

Pollution degree

2

Over voltage category

3

Release characteristic

C

Flush-mounted installation

Frequency

50/60 Hz

Ambient temperature during operating

-25 .. 40°C

Width in number of modular spacings

2

Degree of protection (IP)

IP20

Connectable conductor cross section solid-core

35 .. 35mm²

Connectable conductor cross section multi-wired

35 .. 35mm²

Rated current

20A

Rated fault current

0.3A

Leakage current type

A

Number of poles (total)

2