Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • GEWISS

Technical specifications

Rated permanent current Iu250A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact0
Number of poles3
Number of auxiliary contacts as normally open contact0
Overload release current setting175 - 250A
Degree of protection (IP)IP20
Rated voltage690 - 690V
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz36kA
Position of connection for main current circuitFront side
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Type of control elementRocker lever
Adjustment range undelayed short-circuit release1250 - 2500A
Integrated earth fault protectionNo
Motor drive optionalYes
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device fixed built-in technique
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GWD7305

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • GEWISS

Technical specifications

Rated permanent current Iu

250A

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as change-over contact

0

Number of poles

3

Number of auxiliary contacts as normally open contact

0

Overload release current setting

175 .. 250A

Degree of protection (IP)

IP20

Rated voltage

690 .. 690V

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

36kA

Position of connection for main current circuit

Front side

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Type of control element

Rocker lever

Adjustment range undelayed short-circuit release

1250 .. 2500A

Integrated earth fault protection

Motor drive optional

Complete device with protection unit

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device fixed built-in technique

With under voltage release

DIN rail (top hat rail) mounting optional

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.