Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • GEWISS

Technical specifications

Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu1600A
Number of auxiliary contacts as normally open contact0
Number of poles4
Number of auxiliary contacts as change-over contact0
Rated voltage690 - 690V
Position of connection for main current circuitFront side
Degree of protection (IP)IP20
Type of control elementRocker lever
Motor drive integratedNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Overload release current setting640 - 1600A
Type of electrical connection of main circuitBolt connection
With switched-off indicatorYes
With under voltage releaseNo
Integrated earth fault protectionYes
Adjustment range undelayed short-circuit release2400 - 19200A
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release1600 - 16000A
Motor drive optionalYes
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

GW97623

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • GEWISS

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

1600A

Number of auxiliary contacts as normally open contact

0

Number of poles

4

Number of auxiliary contacts as change-over contact

0

Rated voltage

690 .. 690V

Position of connection for main current circuit

Front side

Degree of protection (IP)

IP20

Type of control element

Rocker lever

Motor drive integrated

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Overload release current setting

640 .. 1600A

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

With under voltage release

Integrated earth fault protection

Adjustment range undelayed short-circuit release

2400 .. 19200A

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

Adjustment range short-term delayed short-circuit release

1600 .. 16000A

Motor drive optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.