Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • GEWISS

Technical specifications

Number of auxiliary contacts as normally open contact0
With integrated under voltage releaseNo
Rated permanent current Iu630A
Number of auxiliary contacts as normally closed contact0
Number of poles3
Overload release current setting252 - 630A
Number of auxiliary contacts as change-over contact0
Motor drive integratedNo
Position of connection for main current circuitFront side
Degree of protection (IP)IP20
Rated voltage690 - 690V
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Type of electrical connection of main circuitBolt connection
Type of control elementRocker lever
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range short-term delayed short-circuit release252 - 630A
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

MV53622

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • GEWISS

Technical specifications

Number of auxiliary contacts as normally open contact

0

With integrated under voltage release

Rated permanent current Iu

630A

Number of auxiliary contacts as normally closed contact

0

Number of poles

3

Overload release current setting

252 .. 630A

Number of auxiliary contacts as change-over contact

0

Motor drive integrated

Position of connection for main current circuit

Front side

Degree of protection (IP)

IP20

Rated voltage

690 .. 690V

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Type of electrical connection of main circuit

Bolt connection

Type of control element

Rocker lever

Integrated earth fault protection

Suitable for DIN rail (top hat rail) mounting

Adjustment range short-term delayed short-circuit release

252 .. 630A

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

Motor drive optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.