Type of control gearLED operating device current-controlled
Connection typePush-in clamp
Colour rendering index CRI80-89
Lamp typeLED not exchangeable
Conductor cross section1.5mm²
Beam angleMedium beam 21-40°
Nominal current250 - 250mA
Suitable for emergency lightingNo
Suitable for number of lamps1
Luminaire with limited surface temperature, sign "D“Yes
Material reflectorPlastic
Emergency power supply integratedNo
Nominal voltage220 - 240V
Rated luminous flux according to IEC 62722-2-17600lm
Colour consistency (McAdam ellipse)SDCM3
Filament test according to IEC 60695-2-11850 °C - 30 s
Constant light output (CLO)No
Type of wiringThrough wiring included
Photobiological safety according to EN 62471RG0
Rated ambient temperature according to IEC62722-2-1-30 - 50°C
Dimming mains voltage modulationNo
Dimming Sine Wave ReductionNo
Dimming potentiometer (integrated)No
Dimming manufacturer's proprietary systemNo
Dimming with push-buttonNo
Luminaire efficacy158lm/W
Max. number of luminaires per miniature circuit breaker B1610
Lumen maintenance at median useful life of 100,000 hr at 25 °C ambient (tq)90%
Max. number of luminaires per miniature circuit breaker C1617
Light distributorFocal lens
Suitable for auxiliary lampNo
Colour temperature adjustableNo
Exchangeable control gearYes
Luminous flux adjustableContinuously variable
Failure rate at median useful life of 100,000 hrs at 25 °C ambient (tq)10%
Degree of protection (IP)IP66
Colour temperature4000 - 4000K