Colour rendering index CRI80-89
Type of control gearLED operating device current-controlled
Conductor cross section1.5mm²
Connection typePush-in clamp
Lamp typeLED not exchangeable
Suitable for emergency lightingNo
Material reflectorPlastic
Suitable for number of lamps1
Nominal current330 - 330mA
Luminaire with limited surface temperature, sign "D“Yes
Emergency power supply integratedNo
Type of wiringThrough wiring included
Rated luminous flux according to IEC 62722-2-19900lm
Beam angleExtreme wide beam >80°
Constant light output (CLO)No
Colour consistency (McAdam ellipse)SDCM3
Nominal voltage220 - 240V
Photobiological safety according to EN 62471RG0
Filament test according to IEC 60695-2-11850 °C - 30 s
Rated ambient temperature according to IEC62722-2-1-30 - 50°C
Dimming potentiometer (integrated)No
Dimming manufacturer's proprietary systemNo
Luminaire efficacy155lm/W
Dimming mains voltage modulationNo
Dimming with push-buttonNo
Dimming Sine Wave ReductionNo
Light distributorReflector
Lumen maintenance at median useful life of 100,000 hr at 25 °C ambient (tq)90%
Max. number of luminaires per miniature circuit breaker C1617
Suitable for auxiliary lampNo
Failure rate at median useful life of 100,000 hrs at 25 °C ambient (tq)10%
Max. number of luminaires per miniature circuit breaker B1610
Luminous flux adjustableNo
Exchangeable control gearYes
Colour temperature adjustableNo
Degree of protection (IP)IP66
Colour temperature5700 - 5700K