Details
- •Luminaires
- •High bay luminaire
- •1 KOM
- •GEWISS
Technical specifications
GWS6044GD30K

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Luminaires
- High bay luminaire
- 1 KOM
- GEWISS
Technical specifications
Mounting method
Pendant
Protection class
I
Emergency power supply integrated
Impact strength
IK07
Nominal voltage
220 .. 240V
Suitable for emergency lighting
Voltage type
AC
Conductor cross section
1.5mm²
Material reflector
Without reflector
Width
376mm
Ball-proof
Colour housing
Grey
Length
434mm
Connection type
Push-in clamp
Material housing
Aluminium
Type of control gear
LED operating device current-controlled
Lamp type
LED not exchangeable
Number of poles
5
Colour rendering index CRI
80-89
Lamp holder
None
Height/depth
171mm
Light sharing
Symmetric
Reflector
None
Degree of protection (IP)
IP65
With light source
With protective cover
With control gear
Colour temperature
3000 .. 3000K
Dimming 1-10 V
Constant light output (CLO)
Suitable for number of lamps
3
Luminaire with limited surface temperature, sign "D“
Dimming 0-10 V
Filament test according to IEC 60695-2-11
650 °C - 30 s
Type of wiring
Ending
Colour of light
White
Beam angle
Medium beam 21-40°
Rated luminous flux according to IEC 62722-2-1
16900lm
Colour consistency (McAdam ellipse)
SDCM3
Photobiological safety according to EN 62471
RG0
Rated ambient temperature according to IEC62722-2-1
-25 .. 40°C
Max. system power
148W
Nominal current
700 .. 700mA
Dimming potentiometer (integrated)
Dimming phase cut-off
Dimming DALI
Dimming DMX
Dimming phase cut-on
Dimming LineSwitch
Dimming mains voltage modulation
Dimming manufacturer's proprietary system
Dimming programmable
Dimming Zigbee
Dimming Sine Wave Reduction
Light distributor
Focal lens
Dimming RF
Dimming Touch and Dim
Dimming with push-button
No dim function
Dimming DSI
Luminaire efficacy
114lm/W
Operation by Bluetooth
Max. number of luminaires per miniature circuit breaker C16
13
Lumen maintenance at median useful life of 100,000 hr at 25 °C ambient (tq)
90%
Exchangeable control gear
Colour temperature adjustable
No
Beam angle adjustable
No
Power factor
0.9
Max. number of luminaires per miniature circuit breaker B16
8
Failure rate at median useful life of 100,000 hrs at 25 °C ambient (tq)
10%
Luminous flux adjustable
Continuously variable
Suitable for auxiliary lamp