1SAM350010R1014 | MS132-25K
Code: 1981325

1SAM350010R1014 | MS132-25K

Rated operation power at AC-3, 230 V
11kW
Phase failure sensitive
Overload release current setting
20 .. 25A
Adjustment range undelayed short-circuit release
375 .. 375A
Rated operation power at AC-3, 400 V
11kW
With integrated auxiliary switch
Device construction
Complete device in housing
With integrated under voltage release
Degree of protection (IP)
IP20
Rated short-circuit breaking capacity lcu at 400 V, AC
50kA
Type of control element
Turn button
Height
112mm
Rated permanent current Iu
25A
Rated operating voltage
250 .. 690V
Switch off technique
Thermomagnetic
With thermal protection
Type of electrical connection of main circuit
Spring clamp connection
Width
45mm
Depth
87mm
Number of poles
3