Technical specifications

Degree of protection (IP)IP30
With integrated under voltage releaseNo
Overload release current setting2000.0 - 5000A
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitBolt connection
Position of connection for main current circuitBack side
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Type of control elementPush button
Integrated earth fault protectionYes
Adjustment range short-term delayed short-circuit release3000.0 - 50000A
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release7500.0 - 75000A
With switched-off indicatorYes
Rated permanent current Iu5000A
Number of poles3
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA071283R1 | E6.2X 5000 Ekip Dip LSIG 3p F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)

IP30

With integrated under voltage release

Overload release current setting

2000.0 .. 5000A

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Bolt connection

Position of connection for main current circuit

Back side

Motor drive integrated

Suitable for DIN rail (top hat rail) mounting

Type of control element

Push button

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

3000.0 .. 50000A

Device construction

Built-in device fixed built-in technique

Motor drive optional

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

7500.0 .. 75000A

With switched-off indicator

Rated permanent current Iu

5000A

Number of poles

3

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

-kA