Technical specifications

Number of auxiliary contacts as normally open contact0
Rated permanent current Iu6300A
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
Number of poles4
Overload release current setting2520.0 - 6300A
Rated voltage690 - 690V
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitConnection at separate chassis part
Degree of protection (IP)IP30
Motor drive integratedNo
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range short-term delayed short-circuit release3780.0 - 63000A
Type of control elementPush button
DIN rail (top hat rail) mounting optionalNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release9450.0 - 94500A
Complete device with protection unitYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz-kA
Integrated earth fault protectionYes
With switched-off indicatorYes
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073299R1 | E6.2X 6300 Ekip Hi-Touch LSIG 4p WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

6300A

With integrated under voltage release

Number of auxiliary contacts as change-over contact

4

Number of poles

4

Overload release current setting

2520.0 .. 6300A

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally closed contact

0

Position of connection for main current circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Motor drive integrated

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Type of control element

Push button

DIN rail (top hat rail) mounting optional

Device construction

Built-in device slide-in technique (withdrawable)

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Complete device with protection unit

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

-kA

Integrated earth fault protection

With switched-off indicator

Motor drive optional