Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as change-over contact0
Overload release current setting87.5 - 125A
Degree of protection (IP)IP20
Motor drive optionalYes
Position of connection for main current circuitFront side
Integrated earth fault protectionNo
Complete device with protection unitYes
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Type of control elementToggle
With switched-off indicatorNo
Adjustment range undelayed short-circuit release625 - 1250A
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalYes
Device constructionBuilt-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release- - -A
Type of electrical connection of main circuitBolt connection
Rated permanent current Iu125A
Number of poles3
Rated voltage240 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user