  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Integrated earth fault protectionNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Overload release current setting87.5 - 125A
Adjustment range undelayed short-circuit release625 - 1250A
Adjustment range short-term delayed short-circuit release- - -A
With integrated under voltage releaseNo
Type of control elementToggle
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Degree of protection (IP)IP20
Type of electrical connection of main circuitBolt connection
With switched-off indicatorNo
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalYes
Rated permanent current Iu250A
Number of poles4
Rated voltage240 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA075251R1 | XT4H 250 TMA 125 625..1250 4p F F UL/CSA

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Integrated earth fault protection

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

0

Position of connection for main current circuit

Front side

Overload release current setting

87.5 .. 125A

Adjustment range undelayed short-circuit release

625 .. 1250A

Adjustment range short-term delayed short-circuit release

- .. -A

With integrated under voltage release

Type of control element

Toggle

Motor drive integrated

Suitable for DIN rail (top hat rail) mounting

Degree of protection (IP)

IP20

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

Motor drive optional

Device construction

Built-in device fixed built-in technique

Complete device with protection unit

DIN rail (top hat rail) mounting optional

Rated permanent current Iu

250A

Number of poles

4

Rated voltage

240 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.