Technical specifications

Rated permanent current Iu250A
Motor drive integratedNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Degree of protection (IP)IP20
Rated voltage240 - 600V
Adjustment range short-term delayed short-circuit release60 - 600A
Type of control elementToggle
Overload release current setting24.0 - 60A
Type of electrical connection of main circuitBolt connection
With switched-off indicatorNo
Position of connection for main current circuitFront side
Number of poles4
Number of auxiliary contacts as change-over contact0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz25kA
DIN rail (top hat rail) mounting optionalYes
Adjustment range undelayed short-circuit release60 - 600A
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Device constructionBuilt-in device fixed built-in technique
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA075365R1 | XT4N 250 Ekip LS/I In=60A 4p F F UL/CSA

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

250A

Motor drive integrated

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

With integrated under voltage release

Degree of protection (IP)

IP20

Rated voltage

240 .. 600V

Adjustment range short-term delayed short-circuit release

60 .. 600A

Type of control element

Toggle

Overload release current setting

24.0 .. 60A

Type of electrical connection of main circuit

Bolt connection

With switched-off indicator

Position of connection for main current circuit

Front side

Number of poles

4

Number of auxiliary contacts as change-over contact

0

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

25kA

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

60 .. 600A

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

Integrated earth fault protection

Device construction

Built-in device fixed built-in technique

Complete device with protection unit