Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Degree of protection (IP)IP20
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitFront side
Number of auxiliary contacts as change-over contact0
Number of auxiliary contacts as normally open contact0
Overload release current setting24 - 60A
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Adjustment range undelayed short-circuit release60 - 600A
With switched-off indicatorNo
Type of control elementToggle
Adjustment range short-term delayed short-circuit release60 - 600A
DIN rail (top hat rail) mounting optionalYes
Device constructionBuilt-in device fixed built-in technique
With under voltage releaseNo
Motor drive optionalYes
Integrated earth fault protectionNo
Suitable for DIN rail (top hat rail) mountingNo
Complete device with protection unitYes
Rated permanent current Iu250A
Number of poles3
Rated voltage240 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz25kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user