Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Degree of protection (IP)IP20
Position of connection for main current circuitFront side
Number of auxiliary contacts as change-over contact0
Overload release current setting60.0 - 150A
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorNo
Type of control elementToggle
Motor drive integratedNo
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
DIN rail (top hat rail) mounting optionalYes
Adjustment range undelayed short-circuit release150 - 1500A
Adjustment range short-term delayed short-circuit release150 - 1500A
Type of electrical connection of main circuitBolt connection
With under voltage releaseNo
Complete device with protection unitYes
Integrated earth fault protectionNo
Rated permanent current Iu250A
Number of poles4
Rated voltage240 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz65kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA075451R1 | XT4H 250 Ekip LSI In=150A 4p F F UL/CSA

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Degree of protection (IP)

IP20

Position of connection for main current circuit

Front side

Number of auxiliary contacts as change-over contact

0

Overload release current setting

60.0 .. 150A

Suitable for DIN rail (top hat rail) mounting

With switched-off indicator

Type of control element

Toggle

Motor drive integrated

Motor drive optional

Device construction

Built-in device fixed built-in technique

DIN rail (top hat rail) mounting optional

Adjustment range undelayed short-circuit release

150 .. 1500A

Adjustment range short-term delayed short-circuit release

150 .. 1500A

Type of electrical connection of main circuit

Bolt connection

With under voltage release

Complete device with protection unit

Integrated earth fault protection

Rated permanent current Iu

250A

Number of poles

4

Rated voltage

240 .. 600V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

65kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.