Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles4
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu250A
Overload release current setting60.0 - 150A
Suitable for DIN rail (top hat rail) mountingNo
Type of electrical connection of main circuitBolt connection
Number of auxiliary contacts as change-over contact0
Position of connection for main current circuitFront side
Rated voltage240 - 600V
Motor drive integratedNo
Degree of protection (IP)IP20
With switched-off indicatorNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz35kA
DIN rail (top hat rail) mounting optionalYes
With under voltage releaseNo
Adjustment range short-term delayed short-circuit release150 - 1500A
Complete device with protection unitYes
Type of control elementToggle
Integrated earth fault protectionYes
Motor drive optionalYes
Device constructionBuilt-in device fixed built-in technique
Adjustment range undelayed short-circuit release150 - 1500A
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA075499R1 | XT4S 250 Ekip LSIG In=150A 4p F F UL/CSA

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

250A

Overload release current setting

60.0 .. 150A

Suitable for DIN rail (top hat rail) mounting

Type of electrical connection of main circuit

Bolt connection

Number of auxiliary contacts as change-over contact

0

Position of connection for main current circuit

Front side

Rated voltage

240 .. 600V

Motor drive integrated

Degree of protection (IP)

IP20

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

35kA

DIN rail (top hat rail) mounting optional

With under voltage release

Adjustment range short-term delayed short-circuit release

150 .. 1500A

Complete device with protection unit

Type of control element

Toggle

Integrated earth fault protection

Motor drive optional

Device construction

Built-in device fixed built-in technique

Adjustment range undelayed short-circuit release

150 .. 1500A