Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Overload release current setting320 - 800A
Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Type of control elementPush button
With switched-off indicatorYes
Degree of protection (IP)IP30
Position of connection for main current circuitBack side
Number of auxiliary contacts as change-over contact4
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
Adjustment range short-term delayed short-circuit release- - -A
Device constructionBuilt-in device fixed built-in technique
Motor drive optionalYes
Adjustment range undelayed short-circuit release1200 - 12000A
Rated permanent current Iu800A
Number of poles3
Rated voltage600 - 600V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA